BUSINESS
Terapicco STS
TERAPICCO STS
ULTRA HIGH SPEED
STATIC TRANSFER SYSTEM
We promise the best stability and performance.
The Static Transfer Switch has a duplex power supply as its input for important and sensitive loads to supply one of these to the load side. If a power failure occurs, the power supply is transferred to the normal one seamlessly to provide stable power supply without power interruption at the load.
This product provides the fastest and most stable power transfer within 500㎲
for all loads in case of load power supply failure by using patented high speed switching method thus providing the optimal solution on areas requiring uninterrupted operation of the load system.
Facilities such as semiconductor, IDC centers, chemical and bio centers consist of products very sensitive to power supply. TERAPICCO is the only transfer switch product capable of perfectly protecting important products that existing duplex power transfer switches cannot protect within the fastest transfer speed of within 500㎲.
TERAPICCO Features
- Device capable of stabilizing the power of all loads, provides the fastest and a stable power transfer within 500㎲
- Power supply possible during release time of MC Coil at the process PLC distributor
- Stable power transfer within 500㎲ at any time upon input power failure, regardless of synchronous/asynchronous
- Power transfer regardless of AC or DC
Power duplexing supply selection switching device
High speed switching technology (patented)
Prevents load shutdown by performing an uninterruptible power supply transfer at a very high speed below 500㎲ at synchronous/asynchronous conditions regardless of load type
Real Time power supply analysis
Capable of providing a stable power supply at all times through real time analysis on duplex power supply to load (analyzing faults affecting the load such as amplitude, power failure, surge, sag, dip, frequency fluctuations, harmonics, etc.)
Overcurrent and short circuit current detection and protection technology (patented)
If the input power supply is unstable due to short circuit incident at the load side, the power transfer switch is protected from the overcurrent/short circuit current and a stable backup power supplied to the load seamlessly.
Duplexing of control power and controller inside the product
The internal control power and control processor are duplexed, resulting in high reliability and long lifespan of product.
Convenient installation and maintenance
As this equipment uses natural convection cooling, there is no noise as with existing method using a fan and maintenance is not necessary.
Power can be supplied seamlessly to the load within 500㎲ even at synchronous/asynchronous input power conditions. (patented)
Main power/ Auxiliary power |
STS output voltage after transfer |
|
Synchronous | ||
Asynchronous |
Main power/ Auxiliary power |
|
Synchronous | |
Asynchronous |
STS output voltage after transfer |
|
Synchronous | |
Asynchronous |
Product has superior reliability and lifespan as its control processor and power supply are duplexed.(patented)
Main power/Auxiliary power | |
Existing ATS/STS | |
TERAPICCO |
Detects overcurrent and short circuit current to protect the power transfer switch. (patented)
- If the input power supply is unstable due to short circuit incident at the load side, the power transfer switch is protected from the overcurrent/short circuit current and a stable backup power supplied to the load seamlessly.
The optimum power supply is selected through real-time power supply analysis
- Capable of providing a stable power supply at all times through real time analysis on duplex power supply to load (analyzing faults affecting the load such as amplitude, power failure, surge, sag, dip, frequency fluctuations, harmonics, etc.)
Convenient installation, no need for maintenance
- As this equipment uses natural convection cooling, there is no noise as with existing method using a fan and maintenance is not necessary.
Differentiation from Existing Products
- Existing STS have a low transfer speed to another power supply of 4~10ms when power problems occur. At this time, instantaneous power failure occurs at the load.
▶ Shutdown occurs on devices sensitive to power supply!! - In the case of existing STS using SCR, line short can occur if the both input sources are asynchronous!!
▶ Can not transfer when input power is asynchronous !!
ATS
- ATS : Mechanical duplex power transfer switch
- Performs mechanical transfer of backup power through ATS if a UPS failure occurs
- ATS operation time:
10ms ~ 100ms
Product specification / Rack Type
I-UHS RMS030
Model Name | I-UHS RMS030 (CB 00 B 12) |
---|---|
Type | 1-phase / 2-pole (With Maintenance Switch) |
Current rating | 30A |
Voltage rating (Selectable) |
100-240 V~ (110V, 115V, 120V, 220V, 230V, 240V) |
Frequency | 50/60 Hz |
Input Synchronization | No practical limit |
Power factor | No practical limit |
Overload capacity | 110%_Fault alarm after 1min |
Short-circuit current | 8000Arms, 0.5 cycle |
Safe install environment | External Circuit Breaker |
Transfer type | High Speed Discrete break-before-make |
---|---|
Total STS Transfer Time | < Max. 500us (Same to Asynchronous) |
Transfer Method | Auto / Manual |
User interface | LED: IN 1, IN 2, SYNC, OUT, FLT, STATUS, COM, Bypass |
RS-485&Ethernet (Option) | STS operational status check |
Dimensions (H W D)(mm) | 19 "× 610 × 2U (19 inch rack mount) |
Weight | 18kg |
Ambient Operation Temp. | Min -20°C, Max 50°C |
Cooling | Natural Cooling System (No FAN) |
Regulatory | KC Registration, IEC 62310-1,2 CE CoC |
Standard Warranty | 36 months |
I-UHS RMS030
Model Name | I-UHS RMS030 (CB 00 B 12) |
---|---|
Type | 1-phase / 2-pole (With maintenance Switch) |
Current rating | 30A |
Voltage rating (Selectable) |
100-240 V~ (110V, 115V, 120V, 220V, 230V, 240V) |
Frequency | 50/60 Hz |
Input Synchronization | No practical limit |
Power factor | No practical limit |
Overload capacity | 110%_Fault alarm after 1min |
Short-circuit current | 8000Arms, 0.5 cycle |
Safe install environment | External Circuit Breaker |
Transfer type | High Speed Discrete break-before-make |
Total STS Transfer Time | < Max. 500us (Same to Asynchronous) |
Transfer Method | Auto / Manual |
User interface | LED: IN 1, IN 2, SYNC, OUT, FLT, STATUS, COM, Bypass |
RS-485&Ethernet (Option) | STS operational status check |
Dimensions (H W D)(mm) | 19 "× 610 × 2U (19 inch rack mount) |
Weight | 18kg |
Ambient Operation Temp. | Min -20°C, Max 50°C |
Cooling | Natural Cooling System (No FAN) |
Regulatory | KC Registration, IEC 62310-1,2 CE CoC |
Standard Warranty | 36 months |
I-UHS RS030
Model Name | I-UHS RS030 (CB 00 B 12) |
---|---|
Type | 1-phase / 2-pole (Without maintenance Switch) |
Current rating | 30A |
Voltage rating (Selectable) |
100-240 V~ (110V, 115V, 120V, 220V, 230V, 240V) |
Frequency | 50/60 Hz |
Input Synchronization | No practical limit |
Power factor | No practical limit |
Overload capacity | 110%_Fault alarm after 1min |
Short-circuit current | 8000Arms, 0.5 cycle |
Safe install environment | External Circuit Breaker |
Transfer type | High Speed Discrete break-before-make |
---|---|
Total STS Transfer Time | < Max. 500us (Same to Asynchronous) |
Transfer Method | Auto / Manual |
User interface | LED: IN 1, IN 2, SYNC, OUT, FLT, STATUS, COM |
RS-485&Ethernet (Option) | STS operational status check |
Dimensions (H W D)(mm) | 19” × 546.5 × 2U (19 inch rack mount) |
Weight | 13kg |
Ambient Operation Temp. | Min -20°C, Max 50°C |
Cooling | Natural Cooling System (No FAN) |
Regulatory | KC Registration, IEC 62310-1,2 CE DoC |
Standard Warranty | 36 months |
I-UHS RS030
Model Name | I-UHS RS030 (CB 00 B 12) |
---|---|
Type | 1-phase / 2-pole (Without maintenance Switch) |
Current rating | 30A |
Voltage rating (Selectable) |
100-240 V~ (110V, 115V, 120V, 220V, 230V, 240V) |
Frequency | 50/60 Hz |
Input Synchronization | No practical limit |
Power factor | No practical limit |
Overload capacity | 110%_Fault alarm after 1min |
Short-circuit current | 8000Arms, 0.5 cycle |
Safe install environment | External Circuit Breaker |
Transfer type | High Speed Discrete break-before-make |
Total STS Transfer Time | < Max. 500us (Same to Asynchronous) |
Transfer Method | Auto / Manual |
User interface | LED: IN 1, IN 2, SYNC, OUT, FLT, STATUS, COM |
RS-485&Ethernet (Option) | STS operational status check |
Dimensions (H W D)(mm) | 19” × 546.5 × 2U (19 inch rack mount) |
Weight | 13kg |
Ambient Operation Temp. | Min -20°C, Max 50°C |
Cooling | Natural Cooling System (No FAN) |
Regulatory | KC Registration, IEC 62310-1,2 CE DoC |
Standard Warranty | 36 months |
Product specification / Wall Type
STS-1000
Model Name | STS-1000 (PC 00 B 12) |
---|---|
Type | 1-phase / 2-pole |
Current rating | 6.5A |
Voltage rating (Selectable) |
100-240 V~ (110V, 115V, 120V, 220V, 230V, 240V) |
Frequency | 50/60 Hz |
Input Synchronization | No practical limit |
Power factor | No practical limit |
Overload capacity | 110%_Fault alarm after 1min |
Short-circuit current | 5000Arms, 0.5 cycle |
Safe install environment | External Fuse or External Circuit Breaker |
Transfer type | High Speed Discrete break-before-make |
---|---|
Total STS Transfer Time | < Max. 500us (Same to Asynchronous) |
Transfer Method | Auto / Manual |
User interface | LED: IN 1, IN 2, SYNC, OUT, FLT, STATUS, COM |
RS-485&Ethernet (Option) | STS operational status check |
Dimensions (H W D)(mm) | 127.5 × 190.6 × 289 (H : Button Include) |
Weight | 4.2kg |
Ambient Operation Temp. | Min -20°C, Max 50°C |
Cooling | Natural Cooling System (No FAN) |
Regulatory | KC Registration, IEC 62310-1,2 CE CoC |
Standard Warranty | 36 months |
STS-1000
Model Name | STS-1000 (PC 00 B 12) |
---|---|
Type | 1-phase / 2-pole |
Current rating | 6.5A |
Voltage rating (Selectable) |
100-240 V~ (110V, 115V, 120V, 220V, 230V, 240V) |
Frequency | 50/60 Hz |
Input Synchronization | No practical limit |
Power factor | No practical limit |
Overload capacity | 110%_Fault alarm after 1min |
Short-circuit current | 5000Arms, 0.5 cycle |
Safe install environment | External Fuse or External Circuit Breaker |
Transfer type | High Speed Discrete break-before-make |
Total STS Transfer Time | < Max. 500us (Same to Asynchronous) |
Transfer Method | Auto / Manual |
User interface | LED: IN 1, IN 2, SYNC, OUT, FLT, STATUS, COM |
RS-485&Ethernet (Option) | STS operational status check |
Dimensions (H W D)(mm) | 127.5 × 190.6 × 289 (H : Button Include) |
Weight | 4.2kg |
Ambient Operation Temp. | Min -20°C, Max 50°C |
Cooling | Natural Cooling System (No FAN) |
Regulatory | KC Registration, IEC 62310-1,2 CE CoC |
Standard Warranty | 36 months |
STS-2000
Model Name | STS-2000 (PC 00 B 12) |
---|---|
Type | 1-phase / 2-pole |
Current rating | 12A |
Voltage rating (Selectable) |
100-240 V~ (110V, 115V, 120V, 220V, 230V, 240V) |
Frequency | 50/60 Hz |
Input Synchronization | No practical limit |
Power factor | No practical limit |
Overload capacity | 110%_Fault alarm after 1min |
Short-circuit current | 5000Arms, 0.5 cycle |
Safe install environment | External Fuse or External Circuit Breaker |
Transfer type | High Speed Discrete break-before-make |
---|---|
Total STS Transfer Time | < Max. 500us (Same to Asynchronous) |
Transfer Method | Auto / Manual |
User interface | LED: IN 1, IN 2, SYNC, OUT, FLT, STATUS, COM |
RS-485&Ethernet (Option) | STS operational status check |
Dimensions (H W D)(mm) | 152.5 × 190.6 × 289 (H : Button Include) |
Weight | 4.3kg |
Ambient Operation Temp. | Min -20°C, Max 50°C |
Cooling | Natural Cooling System (No FAN) |
Regulatory | KC Registration, IEC 62310-1,2 CE CoC |
Standard Warranty | 36 months |
STS-2000
Model Name | STS-2000 (PC 00 B 12) |
---|---|
Type | 1-phase / 2-pole |
Current rating | 12A |
Voltage rating (Selectable) |
100-240 V~ (110V, 115V, 120V, 220V, 230V, 240V) |
Frequency | 50/60 Hz |
Input Synchronization | No practical limit |
Power factor | No practical limit |
Overload capacity | 110%_Fault alarm after 1min |
Short-circuit current | 5000Arms, 0.5 cycle |
Safe install environment | External Fuse or External Circuit Breaker |
Transfer type | High Speed Discrete break-before-make |
Total STS Transfer Time | < Max. 500us (Same to Asynchronous) |
Transfer Method | Auto / Manual |
User interface | LED: IN 1, IN 2, SYNC, OUT, FLT, STATUS, COM |
RS-485&Ethernet (Option) | STS operational status check |
Dimensions (H W D)(mm) | 152.5 × 190.6 × 289 (H : Button Include) |
Weight | 4.3kg |
Ambient Operation Temp. | Min -20°C, Max 50°C |
Cooling | Natural Cooling System (No FAN) |
Regulatory | KC Registration, IEC 62310-1,2 CE CoC |
Standard Warranty | 36 months |